AVK MULTI FIRE HYDRANT, ABOVE-GROUND, PN16

Model N7, ductile iron with traffic break-away design (Type C), double shut-off, DN80

AVK headquater in Skovby Galten, Denmark

Contact

AVK International A/S

Bizonvej 1, Skovby, 8464 Galten, Denmark

Above-ground hydrant model N7 with traffic break-away design (Type C) - double shut-off. For drinking water and neutral liquids to max. 60° C

AVK’s Multi hydrants are available with multiple configurations. The heavy duty materials with extra corrosion protection, the PUR coated disc with high memory effect and the high flow capacity ensure durability and good performance. Series 84/93 is designed with double shut-off system for a continued sealing of the hydrant during maintenance, and with traffic break-away design. The flanges connecting the upper and lower barrel are assembled with special stainless steel bushes designed to break if something hits the hydrant. These bushes are the only spare parts to be replaced in case of a breakdown.
fire
fire
Variant 84/93-003
Connection: Flanged
Material: Ductile Iron
DN: DN80 - DN80
PN: PN16

Features

  • Several Storz outlet configurations available eg. 2 x C, 2 x B, 2 x B + 1 x A, 2 x C + 1 x B, etc.
  • Up to 4 outlets possible
  • Valve seat of dezincification resistant brass
  • Automatic drainage in flush proof design
  • Integrated air valve of brass
  • Disc with ductile iron core coated with PUR (Polyurethane) for maximum memory effect
  • Additional ball shut-off for easy maintenance of the hydrant
  • Stainless steel bushes in the upper barrel flange, protecting against damage at traffic knock down
  • Kv value, DN 80: 1 x 65 outlet: 153 m³/h, 2 x 65 outlet: 153 m³/h
  • Kv value, DN 100: 1 x 65 outlet: 210 m³/h, 2 x 65 outlet: 217 m³/h
  • Drainage: Residual flow, DN 80/100: 17/22 ml – Time for drainage, DN 80/100: 120/215 sec/m.
  • Operating force resistance: MOT = 125 Nm, MST = 250 Nm
  • Hydrant head and lower barrel fusion bonded epoxy coating in compliance with DIN 3476 part 1 and EN 14901. Hydrant head additionally coated with a topcoat of UV resistant polyester coating
  • Upper barrel of heavy duty stainless steel
  • Fully vulcanized ball sealing gasket
  • The gear positioned in the lower part and a loosely plugged connection of the operation pipes, makes the main hydrant sealing remain fully functional at an accidental traffic knock down.

 

Downloads

Datasheet
Certificate(s)

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
Pipe cover
mm
H3
mm
H8
mm
H9
mm
Theoretical
weight/kg
84-080-93-2110101004 80 1000 1886 770 220 55
84-080-93-3110101004 80 1250 2136 1020 220 60
84-080-93-4110101004 80 1500 2386 1270 220 65
Enquiry
Scroll for more info

Components

1. Operation nut Aluminium
2. Straight pin slotted Stainless spring steel 1.4310
3. Washer Stainless steel A2
4. Hydrant head Ductile iron GJS-400-15 (GGG-40)
5. Wiper ring NBR rubber
6. Bearing bush Brass
7. O-ring EPDM rubber
8. Air valve Brass
9. Coupling Aluminium
10. O-ring EPDM rubber
11. Cover with wire Aluminium
12. O-ring EPDM rubber
14. Washer Stainless steel A2
15. Bolt, socket head Stainless steel A2
16. Upper stem rod Stainless steel
17. Upper barrel Ductile iron GJS-400-15 (GGG-40)
19. Washer Stainless steel A2
20. Bolt, socket head Stainless steel A2
21. Breakable bush Stainless steel
22. Adaptor ring Ductile iron GJS-400-15 (GGG-40)
23. O-ring EPDM rubber
24. Lock ring Ductile iron GJS-400-15 (GGG-40)
25. Bolt Stainless steel A2
26. Washer Stainless steel A2
27. Drain pipe Polyamide
28. Clamp half Ductile iron GJS-400-15 (GGG-40)
29. Lower barrel Ductile iron GJS-400-15 (GGG-40)
30. Lower stem rod Stainless steel 1.4021, GJS (GGG), PUR
31. Ring Ductile iron GJS-400-15 (GGG-40)
32. Helical roll pin Stainless spring steel 1.4310
33. Stem guide Ductile iron GJS-500-7 (GGG-50)
34. Stem Stainless steel 1.4021
35. Washer POM
36. Stem nut Brass
37. Locking segment HDPE
38. Ball chamber Ductile iron GJS-400-15 (GGG-40)
39. Ball PP

Test/Approvals

  • Hydraulic test according to EN 1074-6 / W 386-P
  • Approved according to CE Reg. No. 0620-CPR-6122

Standards

  • Designed according to EN 1074 - 6:2008, Design according to EN 14384:2005
  • Standard flange drilling to EN1092-2 (ISO 7005-2), PN16