AVK GATE VALVE, FLANGED

PN10/16 flange drilling, UL/ULC listed/FM approved, post indicator flange and wrench nut, DN50-400

Michael Nielsen, Product Manager, Fire protection and water supply

Contact

Michael Nielsen

Product Manager, fire protection & water supply

Flanged gate valve with post indicator flange, UL/FM approved. For fire protection applications to max. 70° C. Rated working pressure DN 50-300: 250psi/17 bar, DN 350-400: UL: 200psi/13,7 bar. FM 250PSI/17,2 bar

AVK gate valves are designed with built-in safety in every detail. The wedge is fully vulcanized with AVK’s own drinking water approved EPDM rubber compound. It features an outstanding durability due to the ability of the rubber to regain its original shape, the double bonding vulcanization process and the sturdy wedge design. The triple safety stem sealing system, the high strength stem and the thorough corrosion protection safeguard the unmatched reliability.

fire
fire
Variant 45/59-010
Connection: Flanged
Material: Ductile Iron
DN: DN50 - DN400
PN: AWWA C509
Closing direction: Clockwise to Close

Features

  • Fixed, integral wedge nut prevents vibration and ensures durability
  • Wedge fully vulcanized with drinking water approved EPDM rubber and equipped with wedge shoes to provide smooth operation
  • Large conical stem hole in the wedge prevents stagnant water
  • Wedge and body guide rails ensure stable operation
  • Stainless steel stem with rolled threads for high strength
  • Full circle thrust collar provides fixation of the stem and low free running torques
  • Triple safety stem sealing with an NBR wiper ring, a polyamide bearing with four NBR O-rings, and an EPDM rubber manchette
  • Round EPDM bonnet gasket fixed in a recess
  • Countersunk and sealed stainless steel bonnet bolts encircled by the bonnet gasket
  • Full bore
  • Low operating torque
  • Fusion bonded epoxy coating in compliance with DIN 3476 part 1 and EN 14901

Downloads

Datasheet
Appendix
Certificate(s)

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
Flange
drilling
L
mm
H
mm
H3
mm
W1
mm
W2
mm
Theoretical
weight/kg
Notes
45-050-59-016141 50 PN10/16 169 292 383 305 165 25 Not UL listed
45-065-59-016141 65 PN10/16 190 311 394 305 178 29
45-080-59-016141 80 PN10/16 203 307 403 305 191 32
45-100-59-016141 100 PN10/16 229 343 458 305 229 36
45-150-59-016141 150 PN10/16 267 445 585 305 280 51
45-200-59-006141 200 PN10 292 546 718 305 345 77
45-200-59-016141 200 PN16 292 546 718 305 345 77
45-250-59-006B41 250 PN10 330 628 832 305 406 130
45-250-59-016B41 250 PN16 330 628 832 305 406 130
45-300-59-006B41 300 PN10 356 701 943 305 483 195
45-300-59-016B41 300 PN16 356 701 944 305 483 198
45-350-59-016B41 350 PN16 381 893 1158 305 533 288
45-400-59-016B41 400 PN16 406 893 1192 305 597 320
BIM drawings
2D/3D drawings
Enquiry
Scroll for more info

Components

1. Bolt Stainless steel A4
2. Washer Stainless steel A4
3. Wrench nut Cast iron GJL-250 (GG-25)
3. Bolt, hexagon head Stainless steel A4
4. Stem Stainless steel 304
5. Post indicator flange Ductile iron GJS-500-7
6. Washer Stainless steel A4
6. O-ring EPDM rubber
7. O-ring EPDM rubber
8. Bonnet bolt Stainless steel A4
9. Bonnet Ductile iron GJS-500-7
10. Wedge nut Brass, DZR CW626N
11. Bonnet gasket EPDM rubber
12. Body Ductile iron GJS-500-7
13. Wedge Ductile iron, EPDM encapsulated
14. Wiper ring EPDM rubber
15. Bushing Polyamide
16. O-ring EPDM rubber
17. Thrust collar Brass, DZR CW602N
18. Bolt Stainless steel 304
19. Wedge shoe Polyamide

Test/Approvals

  • Seat: 1.5 x PN (in Bar). Body: 2 x PN (in Bar). Closing torque test.
  • FM Approved, UL/ULC listed

Standards

  • Designed according to AWWA C509, Designed according to FM 1120/1130, UL 262
  • Face-to-face dimension according to ANSI B16.10
  • Standard flange drilling to EN1092-2 (ISO 7005-2), PN10/16
0 Files In the package