AVK GATE VALVE, FLANGED, PN10/16

EN 558-2 S.15/DIN F5, DN40-500

AVK headquater in Skovby Galten, Denmark

Contact

AVK International A/S

Bizonvej 1, Skovby, 8464 Galten, Denmark

Flanged gate valve EN 558-2 S.15/DIN F5. For drinking water and neutral liquids to max. 70°C

AVK gate valves are designed with built-in safety in every detail. The wedge is fully vulcanized with AVK’s own drinking water approved EPDM rubber compound. It features an outstanding durability due to the ability of the rubber to regain its original shape, the double bonding vulcanization process and the sturdy wedge design. The triple safety stem sealing system, the high strength stem and the thorough corrosion protection safeguard the unmatched reliability.

Variant 02/60-0035
Connection: Flanged
Material: Ductile Iron
DN: DN40 - DN500
PN: PN16
Closing direction: Clockwise to Close

Features

  • Fixed, integral wedge nut prevents vibration and ensures durability
  • Wedge fully vulcanized with drinking water approved EPDM rubber and equipped with wedge shoes to provide smooth operation
  • Large conical stem hole in the wedge prevents stagnant water
  • Wedge and body guide rails ensure stable operation
  • Stainless steel stem with wedge stop and rolled threads for high strength
  • Full circle thrust collar provides fixation of the stem and low free running torques
  • Triple safety stem sealing with an NBR wiper ring, a polyamide bearing with four NBR O-rings, and an EPDM rubber manchette
  • Round EPDM bonnet gasket fixed in a recess
  • Countersunk and sealed stainless steel bonnet bolts encircled by the bonnet gasket
  • Full bore
  • Low operating torque
  • Fusion bonded epoxy coating in compliance with DIN 3476 part 1 and EN 14901, GSK approved

Downloads

Datasheet
Environmental Product Declaration (EPD)
Appendix
Tender Text
Certificate(s)
Installation, Operation & Maintenance

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
Flange
drilling
L
mm
H
mm
H3
mm
W
mm
F
mm
F1
mm
F2
mm
Theoretical
weight/kg
Notes
02-040-60-014649 40 PN10/16 240 194 269 150 14 18 29 8.0
02-050-60-014649 50 PN10/16 250 209 292 165 14 18 29 9.3
02-065-60-014649 65 PN10/16 270 243 336 185 17 23 34 12
02-080-60-014649 80 PN10/16 280 282 382 200 17 23 34 16
02-100-60-014649 100 PN10/16 300 306 416 220 19 23 34 19
02-125-60-014649 125 PN10/16 325 346 471 250 19 23 34 24
02-150-60-014649 150 PN10/16 350 403 543 285 19 22 34 33
02-200-60-004649 200 PN10 400 490 660 340 24 28 34 54
02-200-60-014649 200 PN16 400 490 660 340 24 28 34 54
02-250-60-004649 250 PN10 450 625 825 422 27 36 47 88
02-250-60-014649 250 PN16 450 625 825 422 27 36 47 88
02-300-60-004647 300 PN10 500 706 934 455 27 36 47 126
02-300-60-014647 300 PN16 500 706 934 455 27 36 47 126
02-350-60-006 350 PN10 550 947 1207 520 32 40 55 278 Valve having an increased bore (400 mm)
02-350-60-016 350 PN16 550 947 1207 520 32 40 55 278 Valve having an increased bore (400 mm)
02-400-60-006 400 PN10 600 959 1249 575 32 40 55 272
02-400-60-016 400 PN16 600 959 1249 575 32 40 55 272
02-450-60-006 450 PN10 650 958 1278 640 32 40 55 360 Valve having a reduced bore (400 mm)
02-450-60-016 450 PN16 650 958 1278 640 32 40 55 360 Valve having a reduced bore (400 mm)
02-500-60-006 500 PN10 700 958 1316 715 32 40 55 379 Valve having a reduced bore (400 mm)
02-500-60-016 500 PN16 700 958 1316 715 32 40 55 379 Valve having a reduced bore (400 mm)
BIM drawings
2D/3D drawings
Enquiry
Scroll for more info

Components

1. Stem Stainless steel 1.4104 (430F)
2. Wiper ring NBR rubber
3. O-ring NBR rubber
4. Bearing Polyamide
5. Bonnet Ductile iron GJS-500-7 (GGG-50)
6. Thrust collar Brass, DZR CW602N
7. Manchette EPDM rubber
8. Bonnet bolt Stainless steel A2, sealed with hot melt
9. Bonnet gasket EPDM rubber
10. Wedge nut Brass, DZR CW626N
11. Wedge Ductile iron, EPDM encapsulated
12. Body Ductile iron GJS-500-7 (GGG-50)
13. Wedge shoe Polyamide

Test/Approvals

  • Hydraulic test according to EN 1074-1 and 2 / EN 12266
  • Seat: 1.1 x PN (in bar), Body: 1.5 x PN (in bar). Operation torque test
  • Belgaqua approved
  • Approved according to DIN-DVGW Certificate NW-6202BN0109
  • Approved according to KIWA Certificate K 6320
  • Approved according to SVGW Certificate No. 0301-4606

Standards

  • Designed according to EN 1074 part 1 & 2, Designed according to EN 1171
  • Face-to-face dimension according to EN 558 Table 2 Basic Series 15
  • Standard flange drilling to EN1092-2 (ISO 7005-2), PN10/16
0 Files In the package