AVK FLANGED SWING CHECK VALVE, 350 PSI / 24 BAR

Resilient seated, spring loaded, UL/ULC listed, drilling PN 10/16

Michael Nielsen, Product Manager, Fire protection and water supply

Contact

Michael Nielsen

Product Manager, fire protection & water supply

Flanged swing check valve - UL/ULC for fire protection applications 0-80º C / 32-176º F

The flanged end check valves are UL and ULC listed and very suitable for use in building riser pipes and sprinkler systems for fire protection. The built-in spring ensures a smooth and non-slam closure of the disc.

fire
fire
Variant 5190/00-001
Connection: Flanged
Material: Ductile Iron
DN: DN50 - DN200
PN: PN 24

Features

  • Installation in both horizontal or vertical line with upward flow
  • Flanged end connections
  • Low pressure drop
  • EPDM leak tight sealing
  • All wetted parts of stainless steel provide superior corrosion resistance
  • Red RAL 3000 2-layer paint, min. 50-150 µ
  • UL and ULC listed

Downloads

Datasheet
Certificate(s)

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
Inch
DN
mm
Flange
drilling
L
mm
Theoretical
weight/kg
5190-050-00-100 50 PN10/16 169 6.3
5190-065-00-100 65 PN10/16 183 9.2
5190-080-00-100 80 PN10/16 198 12
5190-100-00-100 100 PN10/16 218 19
5190-125-00-100 125 PN10/16 248 26
5190-150-00-100 150 PN10/16 270 32
5190-200-00-000 200 PN10 325 54
5190-200-00-100 200 PN16 325 54
Enquiry
Scroll for more info

Components

1. Body ASTM A395 40-60-18
2. Seat Bronze
3. Clapper Stainless steel 304
4. Facing seal EPDM rubber
5. Clamping ring Stainless steel 304
6. Gasket EPDM rubber
7. Spring Stainless steel 304
8. Hinge pin Stainless steel 304
9. Bolt Stainless steel 304
10. Lock nut Stainless steel 304
11. Plug ¼” NPT Carbon steel
12. Plug ½” NPT Carbon steel

Test/Approvals

  • Hydraulic test according to UL 312
  • UL / ULC listed

Standards

  • Designed according to UL 312
  • Standard flange drilling to EN1092-2 (ISO 7005-2), PN10/16